Technical support services
With our strong service technicians, we offer a comprehensive service at site at anytime and anywhere. You can rely on our local service teams to provide professional installation, commissioning, maintenance service on our products and any technical services you need.
Please feel free to contact us 24/7.
TECHNICAL SPECIFICATION
|
Item
|
Description
|
Specification/Technical Data
|
1
|
Manufacturer
|
ANT Engineering Ltd.
|
2
|
Type of panel
|
T-04S
|
3
|
Standard
|
IEC 60439-1, DIN EN 60439-1 (VDE 0660 Part 500)
|
4
|
Rated voltage (Ue)
|
415 V
|
5
|
Rated insulation voltage (Ui)
|
690 V
|
6
|
Impulse withstand voltage (Uimp)
|
6 KV
|
7
|
Rated short-time withstand current
|
50 kA/1s
|
8
|
Construction
|
Assembly
|
Type-Test Assembly (TTA) or Partial Type Test Assembly (PTTA)
|
Functional separation
|
Form 3b
|
Type of panel
|
Indoor type, floor mounting or wall mounted, front access
|
Dimensions
|
Height: 2200, 2600 ( with busbar top unit )
|
Width: 600, 800, 1000, 1200 mm
|
Depth: 600, 800, 1000, 1200 mm
|
Protection rating
|
IP 30 to IP 42 for indoor type; IP 54 for outdoor
|
Material
|
Electro-galvanized sheet steel
|
Thickness
|
2.0 mm
|
Finishing
|
powder coated, wet-paint
|
9
|
Bus-bar (3-pole and 4-pole)
|
Standard
|
IEC 60439-2
|
Rated currents (In)
|
Up to 6300A
|
Rated short-time withstand
|
Up to 65KA/ 1s
|
Arrangement
|
Main horizontal busbar: full length
|
Vertical busbar: full length
|
Bus-bar material
|
Copper Purity 99.9%
|
Bus-bar tinned
|
Yes
|
Bus-bar Size
|
PTTA
|
Bus-bar tap-off to functional unit
|